Double jacketed 3 core screened mains power cable

 

 

 

Cable Specifications:

 


Technical Data:

Core identification code:
Up to 5 cores: According to VDE 0293-308 Appendix T9)
Starting at 6 cores: ÖLFLEX® colour code see Appendix T 7

Based on
IEC 60227-5 HD 21.5 S3
VDE 0281 Part 5
HD 21.13 S1
VDE 0281 Part 13

Specific insulation resistance: > 20 GOhm x cm
Conductor stranding: Fine wire in accordance to VDE 0295 Class 5 / IEC 60228 Class 5
Minimum bending radius: Occasional flexing: 20 x cable diameter ~ Fixed installation: 6 x cable diameter
Rated voltage: Up to 1.0 mm²: U0/U: 300/500 V ~ Starting at 1.5 mm²: U0/U: 450/750 V Fixed, protected installation: U0/U: 600/1000 V
Test voltage: 4000 V
Protective conductor: G = with protective conductor GN/YE ~ X = without protective conductor
Range of temperature: Occasional flexing: -5°C up to +70°C ~ Fixed installation: -40°C up to +80°C

Design
* Fine strands of bare copper wires
* PVC insulation LAPP P8/1
* PVC inner sheath, grey
* Screen made of tinned copper wire braid
* PVC outer sheath, transparent

Product features:
* Flame retardant according to IEC 60332-1-2
* Good chemical resistance see Appendix T1
* High coverage degree of the screen low transfer impedance (max. 250 O/km at 30 MHz)


Close This Window